Table-1 Uv line
Wiring
2-core, non-polarity
Type
Shield wire
Size/Length
AWG18 (0.75 mm
Table-2 Uh line
Wiring
2-core, non-polarity
Type
Shield wire
AWG18 (0.75 mm
Size/Length
AEG14 (2.0 mm
Table-3 Remote controller wiring, Flow Selector unit Multi-port type and Single - port type wiring
Wiring
2-core, non-polarity
Type
AWG20 (0.5 mm
Up to 984 ft (300 m) (L4+L5+L6)
Up to 1312 ft (400 m) in case of wireless remote controller in group control.
Size/Length
Up to 656 ft (200 m) total length of communication wiring between indoor units
and FS unit (Multi-port type and Single-port type) (L5+L6)
Up to 984 ft (300 m) (L4)
• U (v, h, c) line means of control wiring.
Uv line: Between indoor and outdoor units.
Uh line: Central control line.
Uc line: Between outdoor and outdoor units.
<U series>
Central controller device
L1
<SHRM-u>
Outdoor unit
(SHRM-u)
L2
<U series>
Indoor unit
Remote controller
Flow Selector
Multi port type FS unit and single port
type FS unit
45-EN
2
) to AWG16 (1.25 mm
2
) : Up to 3280 ft (1000 m)
2
) to AWG16 (1.25 mm
2
) : Up to 3280 ft (1000 m)
)
: Up to 6561 ft (2000 m)
2
2
) to AWG14 (2.0 mm
2
)
<U series>
L3
<U series>*
(DN14=1)
(DN14=2)
(DN14=2)
L4
L5
<U series>*
L6
Remote controller
– 23 –
REQUIREMENT
• For the central control line (L1) when U-series outdoor units and outdoor units other than U-series are connected
to the central control device, follow the communication wiring specifi cations for outdoor unit other than U-series.
• Using the same wire type and size, wire each line below.
If the different wire types and sizes are mixed in each line, communication trouble is caused.
• Central control line and wiring between indoors and outdoor units other than SHRM-u and U-series
• Uv line (wiring between indoor and outdoor units) and Uc line (wiring between outdoor and outdoor units) in
SHRM-u and U-series
• Wiring between outdoor and outdoor units other than SHRM-u and U-series
• For communication wiring specifi cations for outdoor unit other than SHRM-u, refer to the Installation Manual
attached to the outdoor unit to be connected.
[Uh-line and line / wiring between outdoor and indoor units other than SHRM-u and U series]
Up to 6561 ft (2000 m) (L1 + L10 + L11)
[Uv line and Uc line in U series]
Up to 3280 ft (1000 m) (L2, L3)
Up to 3280 ft (1000 m) (L8 + L9)
[Between outdoor and outdoor units other than SHRM-u and U series
Up to 328 ft (100 m) (L12)
Outdoor unit
(SMMS-u)
L9
L8
Indoor unit
* Even if the indoor units, the remote controllers, and the central control device are models other than U series
<Other than U series>
Outdoor unit
(SMMS-i)
(SMMS-e)
(MiNi SMMS)
etc.
L11
L10
<U series>*
Indoor unit
<U series>*
Remote controller
L12