Descargar Imprimir esta página

HP Latex 260 Guía De Preparación Del Sitio página 9

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 50
Table 2-3
Single phase line specifications (continued)
Maximum load current (per power cord)
Active power consumption
WARNING!
Fault Circuit Interrupter) operates in the case of a leakage current fault to the product chassis, even
when an isolation device (such as an isolating transformer) is used to supply power to the printer.
CAUTION:
Ensure that the input voltage is within the printer's rated voltage range. The printer
requires a step-up transformer for tri-phase 208 V or 200 V power systems (voltage line to line).
Circuit breakers
NOTE:
The circuit breakers must meet the requirements of the printer and shall be in accordance with
the Electrical Code requirements of the local jurisdiction of the country where the equipment is installed.
The printer requires two dedicated lines, each protected by a branch circuit breaker according to the
rating of the wall socket outlet.
Table 2-4
Circuit breaker specifications
Single phase line
* Rating according to wall socket outlet
1
NOTE:
The Power Distribution Unit (PDU) must be rated to meet the power requirements of the printer,
and shall be in accordance with the Electrical Code requirements of the local jurisdiction of the country
where the equipment is installed.
Figure 2-1
Electrical configuration diagram
ENWW
Outside Japan
15 A
2.6 kW
Ensure that the printer's built-in Residual Current Circuit Breaker (also known as Ground
Branch circuit breaker
2 poles, 16 A * (20A for NEMA 6-20R
wall socket)
Japan only
15 A
2.6 kW
Quantity
2, one for each dedicated line
1
Electrical configuration
5

Publicidad

loading

Este manual también es adecuado para:

Designjet l26100 serieDesignjet l26500 serieLatex 210