Install the Indoor Unit
1. Engage the slots on the Indoor Unit to the hooks of installation plate 1 .
Ensure the hooks are properly seated on the installation plate by
moving it left and right.
2. Fix the screws 5 to the holes on the hooks of installation plate 4 ,
as illustrated below.
Slots
Indoor Unit back
Typical Piping Installation
Air-to-Water Heatpump
Outdoor Unit
Water piping installation
• Please engage a licensed water circuit installer to install this water
circuit.
• This water circuit must comply with relevant European and national
regulations (including EN61770), and local building regulation codes.
• Ensure the components installed in the water circuit could withstand
water pressure during operation.
• Do not use worn out tube or detachable hose-set.
• Do not apply excessive force to pipes that may damage the pipes.
• Choose proper sealer which can withstand the pressures and
temperatures of the system.
• Make sure to use two spanners to tighten the connection. Further tighten
the nuts with torque wrench in specified torque as stated in the table.
• Cover the pipe end to prevent dirt and dust when inserting it through
a wall.
• If non-brass metallic piping is used for installation, make sure to insulate
the pipes to prevent galvanic corrosion.
Installation plate 1
Hooks
Wall
Installation plate 4
Screws 5
Note: Do not lift the Indoor
Unit by holding the water
pipes to prevent damage of
the pipes.
Temporary
Double Check
connection to be
Valve assembly
removed immediately
is acceptable in
after fi lling water
house
Servicing
Servicing
Valve
Valve
Fan Coil Unit
Main
Radiator/
Water
Floor Heater
Supply
2-Way Valve
• Do not connect galvanised pipes, this will cause galvanic corrosion.
• Use correct nut for all Indoor Unit tube connections and clean all tubes
with tap water before installation. See Tube Position Diagram for detail.
Tube Connector
Nut Size
g & h
RP 1¼"
i & j
Torque wrench
Water Inlet
Do not over tighten, over tightening cause water leakage.
• Make sure to insulate the water circuit pipes to prevent reduction of
heating capacity.
• After installation, check the water leakage condition in connection area
during test run.
• Failure to connect the tube appropriately might cause the Indoor Unit
malfunction.
• Protection From Frost:
If the Indoor Unit is being exposed to frost while power supply failure or pump
operating failure, drain the system. When water is idle inside the system,
freezing up is very likely to happen which could damage the system. Make
sure the power supply is turned off before draining. Backup heater 9 may
be damaged under dry heating.
(A) Space Heating/Cooling Pipework
•
Connect Indoor Unit Tube Connector
Panel/Floor heater.
•
Connect Indoor Unit Tube Connector
Panel/Floor heater.
•
Failure to connect the tube appropriately might cause the Indoor Unit
malfunction.
•
Refer below table for the rated fl ow rate of each particular Outdoor Unit.
Model
WH-WDG05LE5*
WH-SDC0509L3E5,
WH-WDG07LE5*
WH-SDC0509L6E5
WH-WDG09LE5*
* Do not install automatic air purge valves on indoor water pipes.
In the unlikely event that the R290 refrigerant leaks into the
water circuit, there is a risk that the refrigerant will leak indoors.
(B) Circulating Pipework
•
Connect Indoor unit Tube Connector
•
Connect Indoor Unit Tube Connector
•
Failure to connect results in an error stop the system.
Water piping between outdoor unit and indoor unit
Model
Inner
diameter
WH-WDG05LE5*
ø20
WH-WDG07LE5*
ø25
WH-WDG09LE5*
Torque
117.6 N•m
RP 1"
88.2 N•m
Spanner
Water outlet (To Outdoor Unit)
Water inlet (From Outdoor Unit)
Water Outlet
CAUTION
to outlet connector of Zone 1
a
to inlet connector of Zone 1
b
Rated Flow Rate (l/min)
Cool
14.3
20.1
23.5
to outdoor unit inlet water socket.
d
c
to outdoor unit outlet water socket.
Maximum
Insulator
Maximum
length
thickness
30 mm
30 m
or more
Heat
14.3
20.1
25.8
Elevation
10 m
5