Operation
11. Disconnect the system components which cannot be flushed from the
refrigerant circuit. These components include:
– Compressor
– Line filter
– Fixed choke
– Collection containers
– Filter drying units
– Expansion valve
12. Connect the components for flushing to the service ports (14) and (15)
of the AirCon Service Center using special adapters and in accord-
ance with the manufacturer's specifications to form a flushing circuit.
NOTE
I
Observe the guidelines on repairs from the vehicle manufacturer.
13. In the basic menu, use the cursor keys
"Other selections":
14. Press ENTER to confirm.
15. Use the cursor keys
16. If necessary, use the keypad (7) to enter the data and press ENTER to
confirm.
If no data is to be entered, press ENTER to switch to the next program
step.
17. Use the cursor keys
conditioning system or just individual components:
18. Press ENTER to confirm.
19. Follow the instructions in the display.
104
Short selection
Free selection
Other selections
ENTER-OK
or
to select "Flushing":
Flushing
Reset scales.
Service.
ENTER-OK STOP-EXIT
or
to select whether to flush the entire air
Full flushing
Fast flushing
ENTER-OK STOP-EXIT
AirConServiceCenter
or
to select
EN