Technical Data
General
Standards
Voltage
Voltage range
Reference (Max) current
Start current
Power consumption of current circuit < 1,8 VA
Frequency
Accuracy of measurement
Memory backup
Temperature range
Material of front cover
Material of back cover
Resistance to heat and fire
Protection against penetration of
dust and water
Connection area, current connecting 4 – 25 mm
terminals
Pulse output
Standard
Connection area, connecting terminal 0.5 – 2.5 mm
Recommended torque value
External pulse voltage
Max. current
Pulse length
Pulse frequency
LED
Pulse frequency
Pulse length
Display
Type
Digits height
Clock
Standard
Clock backup
Clock accuracy
*) To comply with the protection requirements the meter must be
mounted in a class IP 51 enclosure or better, according to IEC 60529.
IEC 62052-11, IEC 62053-21,
EN 50470-1, EN 50470-3
230 V AC
-23% to +20%
10 (80) A
25 mA
50/60 Hz (±5%)
Class B (Cl 1, ±1%)
EEPROM
-40 to +55
Polycarbonate
Polycarbonate/glass fiber
IEC 695-2-1
IP 20 *)
IEC 62053-1 (SO)
0.5 Nm
5 – 40 V DC
100 mA
100 ms
100 imp/kWh
1000 imp/kWh
40 ms
LCD with 6 digits
6 mm
IEC 62054-21
SuperCap. 48h
Net supply : ±5s / 30 days
(at normal frequency and
operating conditions)