NOTE: Use [UP/DOWN] to toggle between the screens.
1
Time/Date
2
User Unit:
3.  Use control push buttons to select and change required parameter.
4.  Press [ENTER] to accept the parameter changes.
NOTE: Pressing [ESCAPE] toggles to the upper menu.
Right button [ 8   ]
Up Button [ h ]
Left button [ ESC ] 
Down button [   i  ]
5.  Use control push buttons to:
Accept changes and leave menu
Do not accept changes and leave menu
Return to the System menu.
5.4
Calibration
5.4.1
Calibration (4 - 20 mA)
Channel boards are configured to accept 4 - 20 mA input signals from two-wire or three-wire remote transmitters. The 
controller does not require any calibration.
During calibration of MSA's Ultima X Gas Monitors, the GasGard XL unit shows the following:
• For combustibles and toxics, if cal enable is ON, the 3.75 mA signal does not show a fault or underrange state on the 
GasGard XL unit. The display may show 0 or some negative value, depending on the Dead Band Around Zero 
setting.
• For oxygen, if cal enable is ON, the 21 mA signal causes the GasGard XL to go into an overrange status. As soon as 
the signal drops below 20.4 mA, the user must clear this state by pressing the RESET button.
US
• ADR – unit IP address
• MASK - subnetwork mask 
• GATE -gateway
Define time or date format (dd.mm. or mm.dd) can be selected.
Define measuring units. 
GasGard XL
5 Configuration