CONNECTIONS TO THE TERMINAL BLOCK AND STANDARD OPERATION
LP1
OUTPUT
LAMP
OUTPUT
SC-COM
OUTPUT
24Vcc-COM
OUTPUT
Foto-COM
INPUT (NC) External photocell
ST-COM
INPUT (NC) Stop
PP-COM
INPUT (NA) Step-by-step
ANT-GND
INPUT
COM-ENC-5V INPUT
AP-CH
OUTPUT
18-0
INPUT
VM-0
INPUT
ADJUSTMENTS
TRIMMER FORZA AP Trimmer to set the opening force, from 0 to 650 N / 1.000 N
TRIMMER FORZA CA Trimmer to set the closing force, from 0 to 650 N / 1.000 N
TRIMMER TEMPO PAUSA To set the pause time from a minimum of 0 seconds up to a maximum of 90 seconds and
OPTIONS TO STANDARD OPERATION
DIP SWITCH N° 1: ON Enables automatic closing. After a complete opening cycle, when the PAUSE TIME set by the
DIP SWITCH N° 2: ON The step-by-step command becomes shared. The step-by-step command usually only
PROGRAMMING OPENING AND CLOSING DISTANCES
Put the door in the position where it is connected to the trolley halfway along its length of travel
Press the pushbutton S1 and keep it pressed for at least 5 seconds; the LED DL1 lights up immediately. As soon
as the pushbutton is released the LED DL1 starts blinking (showing that the programming phase is active). Give
the command for opening within 10 sec. (otherwise there is automatic exit from programming).
The door starts an automatic cycle of measuring distances.
The first movement is opening until the stop for the open position is detected, at which point the movement is
automatically reversed until total closure.
At the end of the automatic opening and closing cycle, exit from the programming phase and store the opening and
closing distances.
If the automatic opening and closing cycle has been carried out correctly, the procedure is finished. If there are any
problems, the whole procedure must be repeated.
Connection/cutting out of reversal for 1 or 2 mm after closing
1 – disconnect from the power supply
2 – press the pushbutton S1 and keep it pressed
3 – connect to the power supply
The function is alternately connected and disconnected.
Courtesy light
Flashing light
Open gate indicator light
Accessories power supply 24Vcc 300mAmax
Antenna
Encoder
Motor CC
Board power supply
Motor CC power supply
only active if automatic reclosing is set (dip N° 1 a ON)
trimmer has elapsed, the gate closes automatically
generates opening
Fixed voltage 24V for motor operating time. 24V 25Wmax
(2 x 24V 15W H70/11CC)
Tension free contact closed for operating time. 24÷230Vac
40Wmax
Always ON during the opening, pause and closing cycle.
24Vcc 2Wmax
Ignored during opening; during closing the direction of
movement is reversed even without removing the obstacle
Generates the immediate stopping of movement in any
position
Operating
sequence:
control unit is switched on, the first command is Open
For radio board
18 V
pagina 5
open-stop.-close-stop...after
the