Descargar Imprimir esta página

Danfoss OPTYMA Plus Manual De Instrucciones página 5

Ocultar thumbs Ver también para OPTYMA Plus:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 19
Instructions
13 – Maintenance
Always switch off the unit at main
switch before opening the fan door
(s).
Internal pressure and surface tem-
perature are dangerous and may
cause
permanent
nance
operators
require appropriate skills and tools.
Tubing temperature may exceed
100°C and can cause severe burns.
Ensure that periodic service inspec-
tions to ensure system reliability and
as required by local regulations are
performed.
To prevent system related problems, following
periodic maintenance is recommended:
• Verify that safety devices are operational and
properly set.
• Ensure that the system is leak tight.
• Check the compressor current draw.
• Confirm that the system is operating in a way
consistent with previous maintenance records
and ambient conditions.
• Check that all electrical connections are still
adequately fastened.
• Keep the unit clean and verify the absence
of rust and oxidation on the unit compo-
nents, tubes and electrical connections.
The condenser must be checked at least once
a year for clogging and be cleaned if deemed
necessary. Access to the internal side of the
condenser takes place through the fan door.
Microchannel coils tend to accumulate dirt on
the surface rather than inside, which makes
them easier to clean than fin-&-tube coils.
• Switch off the unit at main switch before ope-
ning the fan or side door.
17 - Fan speed controller setting (Not factory premounted)
Fan speed Controller
FSC type
Spare part number
061H3140
XGE-4C
When Fan speed Controller is at factory setting (19 bar):
- Maximum number of turns allowed in clockwise direction (+) = 4.
- Maximum number of turns allowed in anti-clockwise direction (-) = 6
© Danfoss | DCS (CC) | 2021.11
• Remove surface dirt, leaves, fibres, etc. with
a vacuum cleaner, equipped with a brush or
other soft attachment. Alternatively, blow com-
pressed air through the coil from the inside out,
and brush with a soft bristle. Do not use a wire
brush. Do not impact or scrape the coil with the
injury.Mainte-
vacuum tube or air nozzle.
and
installers
• Before closing the fan door, turn the fan blade
in a safe position, to avoid that the door hits the
fan.
If the refrigerant system has been opened, the
system has to be flushed with dry air or nitrogen
to remove moisture and a new filter drier has to
be installed. If evacuation of refrigerant has to be
done, it shall be done in such a way that no refrige-
rant can escape to the environment.
14 – Declaration of incorporation
• Pressure Equipment Directive 2014/68/EU
EN 378-2:2016 - Refrigerating systems and Heat
Pumps - Safety and environmental requirements-
Parts 2: Design, construction, testing, marking
and documentation.
Low Voltage Directive 2014/35/EU EN 60335-
1:2012 + A11:2014- Household and similar elec-
trical appliances-Safety-Part 1: General require-
ments-for all above mentioned condensing units
Eco-design DIRECTIVE 2009/125/ EC, esta-
blishing a framework for the setting of Eco-design
requirements for energy-related products.
REGULATION (EU) 2015/1095, implementing Eco-
design Directive 2009/125/EC with regard to Eco-
design requirements for professional refrigerated
storage cabinets, blast cabinets, condensing units
and process Chiller.
• Condensing unit measurements are made accor-
ding to standard "EN 13771-2:2017" – Compressor
Refrigerant
letter
R404A/R507/R448A/R449A/R452A
X
If refrigerant used is R134a or R513A
Factory
For Refrigerant
setting
19 bar
and condensing units for refrigeration-perfor-
mance testing and test methods- part 2: Conden-
sing units.
15 - Warranty
Always transmit the model number and serial
number with any claim filed regarding this pro-
duct.
The product warranty may be void in following
cases:
• Absence of nameplate.
• External modifications, in particular, drilling,
welding, broken feet and shock marks.
• Compressor opened or returned unsealed.
• Rust, water or leak detection dye inside the
compressor.
• Use of a refrigerant or lubricant not approved
by Danfoss.
• Any deviation from recommended instructions
pertaining to installation, application or main-
tenance.
• Use in mobile applications.
• Use in explosive atmospheric environment.
• No model and serial number transmitted with
the warranty claim.
16 – Disposal
Danfoss recommends that condensing
units and oil should be recycled by a sui-
table company at its site.
Action required*
360°=1 turn = Approx 1.5 bar
(Clockwise rotation =
Increase pressure setting,
Counter clockwise rotation =
Decrease pressure setting)
Turn the adjusting screw towards counter-
clockwise (-) by 6 turns to set the pressure
from 19 bar to 10 bar.
118A2984A - AN37374141535501-010101 | 5

Publicidad

loading

Este manual también es adecuado para:

Op-mpxm