CAUTION
Limit value 1 (LV1)
Terminals 1,2,3
Limit value 2 (LV2)
Terminals 4,5,6
Description of the relay outputs
All relay outputs are designed as neutral contacts. This means the full
range of connection options is available to you. This facilitates the
switching of mains power, external power and direct switching of
inputs, e.g. a process control procedure is implemented.
Durability of relays
Please note the loading capacity of the relay and the overall loading
capacity (see Technical Data)!
Excessive loading may destroy the relay.
LV1 and LV2 limit value outputs
Two isolated relay contacts are provided to issue limit value exceed-
ed alerts. For both contacts, the limit values, the number of times the
limit value has been exceeded up to switching as well as the switch-
ing function itself are freely programmable:
Function
Contact
LV1
Isolated change-over con-
tact
relay switches
Terminal 1: c / Central contact
when exceed-
Terminal 2: no / closing contact
ing the limit
Terminal 3: nc / Break contact
value of
limit value 1
Function
Contact
LV2
Isolated change-over
contact
Relay switches
Terminal 4: c / central contact
when exceeding
Terminal 5: no / closing contact
the limit value of
Terminal 6: nc / break contact
limit value 2
Further explanations can be found in the section
LV1 and LV2 limit value
Input basic programming data
Action
programmable:
- Permanent contact
- Impulse
(1-99 seconds/minutes)
- interval
(1-99 seconds/minutes)
- Area of lower limits
- Switches when the limit
value is exceeded once, twice
or three times
Action
programmable:
- Permanent contact
- Impulse
(1-99 seconds/minutes)
- interval
(1-99 seconds/minutes)
- Area of upper limits
- Two-point
- Switches when the limit
value is exceeded once, twice
or three times
outputs"!
"Operating mode of
41