Table 3.2: Configuration of the switches to select the type of analog input and output signal on the
Input/
Setting of
Signal
Output
Switches
Voltage
S1.1 = OFF
AI1
Current
S1.1 = ON
Voltage
S2.1 = OFF
AI2
Current
S2.1 = ON
Voltage
S1.2 = ON
AO1
Current
S1.2 = OFF
NOTE!
Configuration to connect the RS485:
S1.3 = ON and S1.4 = ON: terminal RS485 ON.
S1.3 = OFF and S1.4 = OFF: terminal RS485 OFF.
Any other combination of the switches is not allowed.
NOTE!
Configuration to connect the RS485:
S2.3 = ON and S2.4 = ON: terminal RS485(2) ON.
S2.3 = OFF and S2.4 = OFF: terminal RS485(2) OFF.
Any other combination of the switches is not allowed.
CFW500-CRS485
Signal
Range
0...10 V
P0233 = 0 (direct reference) or 2 (inverse reference)
0...20 mA
P0233 = 0 (direct reference) or 2 (inverse reference)
4...20 mA
P0233 = 1 (direct reference) or 3 (inverse reference)
0...10 V
P0238 = 0 (direct reference) or 2 (inverse reference)
0...20 mA
P0238 = 0 direct reference) or 2 (inverse reference)
4...20 m A
P0238 = 1 (direct reference) or 3 (inverse reference)
0...10 V
P0253 = 0 (direct reference) or 3 (inverse reference)
0...20 mA
P0253 = 1 (direct reference) or 4 (inverse reference)
4...20 mA
P0253 = 2 (direct reference) or 5 (inverse reference)
Installation and Connection
Parameter Setting
CFW501 | 19