Seq
Indication on the Display / Action
11
If necessary, modify the content of "P0402 –
Motor rated rotation", or press the key  for
the next parameter.
12
If necessary, modify the content of "P0403 –
Motor rated frequency", or press the Key  for
the next parameter.
13
If necessary, modify the content of "P0404 –
Motor rated power", or press the key  for the
next parameter.
14
If necessary, modify the content of "P0407 –
Motor rated power factor", or press the key 
for the next parameter.
15
At this point, the HMI shows the option to do the
self-adjustment. Whenever possible, perform
the self-adjustment. Thus, to activate the self-
adjustment, change the value of P0408 to "1".
Figure 5.3 (cont.): Sequence of the Startup group for V V W control
Powering up and Startup
Seq
Indication on the Display / Action
16
During the Self-Adjustment the HMI will
simultaneously indicate the status of
"RUN" and "CONF".
17
At the end of the Self-Adjustment, the value
of P0408 automatically returns to "0", as
well as the Status of "RUN" and "CONF"
are cleared.
Press the key  for the next parameter.
18
The result of Self-Adjustment is the value
in ohms of the motor stator resistance
shown in P0409.
This is the last parameter of the Self-
Adjustment of the V V W control mode.
Press the key  to return to initial
parameter P0202.
19
To exit the STARTUP menu, just press
BACK/ESC.
20
Through the keys  and , select the
desired menu or press the key BACK/ESC
again to return directly to the monitoring
mode of the HMI.