Control Circuit
The control terminal board is equipped with screwless terminals. Always use wires
within the specification listed below. For safe wiring it is recommended to use solid
wires or flexible wires with ferrules. The stripping length respectively ferrule length
should be 8 mm.
EMC Filter Installation
This drive has been tested in accordance with European standards EN61800-3. In
order to comply to the EMC standards, wire the main circuit as described below.
1. Install an appropriate EMC noise filter to the input side.See the list above or
refer to the instruction manual for details.
2. Place the drive and EMC noise filter in the same enclosure.
3. Use braided shield cable for the drive and motor wiring
4. Remove any paint or dirt from ground connections for minimal ground
impedance
5. Install an AC reactor at drives smaller than 1 kW for compliance with the
EN61000-3-2. Refer to the instruction manual or contact your supplier for
details
N
L1
PE
Cable clamp
E
L1
N
EMC
Filter
Wiring distance as
short as possible
Cable shield
grounding clamp
EMC Standards Compliant Wiring of Single- and Three Phase Units
I67E-EN
V1000 Quick Start Guide
Wire Type
Solid
Flexible
Flexible with ferrule
Panel or mounting wall
Metal plate
Grounding Surface
(remove any paint)
R/L1 S/L2 T/L3
U/T1 V/T2 W/T3
(remove any
Braid shielded motor
cable
Ground shield at
motor side
M
Wire size
0.2 to 1.5 mm²
0.2 to 1.0 mm²
0.25 to 0.5 mm²
L2
L3
L1 PE
Cable clamp
L3 L2 L1
EMC
Drive
Filter
Grounding
Surface
paint)
Wiring distance as
short as possible
3 Electrical Installation
Panel or mounting wall
Metal plate
Grounding Surface
(remove any paint)
E
R/L1 S/L2 T/L3
U/T1 V/T2 W/T3
R/L1 S/L2 T/L3
U/T1 V/T2 W/T3
Cable shield
grounding clamp
M
Drive
Grounding
Surface
(remove any
paint)
Braid shielded motor
cable
Ground shield at
motor side
11