Frequency Reference And Acceleration/ Deceleration Times - Omron V1000 Guía Rápida De Referencia

Ocultar thumbs Ver también para V1000:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 64

Frequency Reference and Acceleration/ Deceleration Times

Frequency Reference Setup(b1-01)
Set parameter b1-01 according to the frequency reference used.
b1-01
Reference source
0
Operator keypad
1
Analog input
2
Serial Comm.
3
Option Board
4
Pulse input
Acceleration/ Deceleration Times and S-Curves
There are four sets of acceleration and deceleration times which can be set in the
C1-
parameters. The default activated accel/ decel times are C1-01/02. Adjust
these times to the appropriate values required by the application. If necessary S-
curves can be activated in the C2-
end.
Test Run
Perform the following steps to start up the machine after all parameter settings have
been done.
1. Run the motor without load and check if all input, outputs and the sequence
work as desired.
2. Connect the load to the motor.
3. Run the motor with load and make sure that there is no vibrations, hunting or
motor stalling occurs.
After taking the steps listed above, the drive should be ready to run the application
and perform the basic functions. For special setups like PID control etc. refer to the
instruction manual.
I67E-EN
V1000 Quick Start Guide
Set the frequency references in the d1-
inputs to switch over between different reference values.
Apply the frequency reference signal to terminal A1 or A2.
Serial Communications using the RS422/485 port
Communications option card
Set the frequency reference at terminal RP using a pulse train signal.
parameters for softer accel/ decel start and
Frequency reference input
5 Start Up
parameters and used digital
21