Mechanical Installation; Upon Receipt; Installation Environment - Omron V1000 Guía Rápida De Referencia

Ocultar thumbs Ver también para V1000:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 64
2

Mechanical Installation

Upon Receipt

Please perform the following tasks after receiving the drive:
• Inspect the drive for damage. If the drive appears damaged upon receipt, contact
your supplier.
• Verify receipt of the correct model by checking the information on the nameplate.
If you have received the wrong model contact your supplier.

Installation Environment

For optimum performance life of the drive, install the drive in an environment that
meets the conditions listed below.
Environment
Installation Area
Ambient
Temperature
Humidity
Storage
Temperature
Surrounding Area
Altitude
Vibration
Orientation
I67E-EN
V1000 Quick Start Guide
Indoors
°
°
-10
C to +40
C (NEMA Type 1)
°
°
-10
C to +50
C (Open-Chassis Type)
When using an enclosure panel, install a cooling fan or air conditioner
in the area to ensure that the air temperature inside the enclosure does
not exceed the specified levels.
Do not allow ice to develop on the drive.
95% RH or less and free of condensation
°
°
-20
C to +60
C
Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water or other foreign materials
• radioactive materials
• combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight
1000 m or less
2
10 - 20 Hz at 9.8 m/s
Install the drive vertically to maintain maximum cooling effects.
2 Mechanical Installation
Conditions
, 20 - 55 Hz at 5.9 m/s
2
7

Hide quick links:

Publicidad

Tabla de contenido
loading

Tabla de contenido