DC connection
40 / 40 A*
* MPPT 1 / MPPT 2.
Below we indicate the admitted section limits in the connections. The minimum sections indicated may not be
enough relative to the type of installation, so the installer must size the wiring relative to its needs.
In accord with the current circulating through the conductors (maximum
16 mm
2
In accord with the current circulating through the conductors (maximum
16 mm
2
Furthermore, for sizing the wire, keep in mind the range of admitted diameters by the M25 packing glands
supplied by Ingeteam installed in the unit. This range is from 7 ~ 17 mm.
ABO2011IQM01_A - Installation and Operation Manual
Maximum DC current input in TL M units
Terminal connections in S and S+ versions
28TL M
33TL M
40 / 40 A*
DC input sections in TL units
Terminal connections in S and S+ versions
28TL
for a solid nucleus cable, 50 mm
70 mm
for a semi-rigid cable nucleus)
2
DC input sections in TL M units
Terminal connections in S and S+ versions
28TL M
33TL M
for a solid nucleus cable, 35 mm
50 mm
for a semi-rigid cable nucleus)
2
40TL M480
40 / 40 A*
33TL
for a flexible nucleus cable or
2
40TL M480
for a flexible nucleus cable or
2
Ingeteam
DE
EN
ES
FR
IT
PT
119