PIPELINE SIZE TABLE TBML 160 PN
SIPHON FEED SYSTEM WITH FEED FROM THE TOP OF THE TANK
1 Tank
3 Wire-net filter
4 Pump
6 Suction pipe
7 Return pipe
10 Bottom valve
GRAVITY SUPPLY SYSTEM
1 Tank
2 Feeding pipe
3 Wire-net filter
4 Pump
5 Degasifier
PUMP AXIS
1 Tank
3 Wire-net filter
4 Pump
6 Suction pipe
7 Return pipe
PUMP AXIS
SUCTION FEED SYSTEM
PUMP AXIS
Note: For any missing devices in the piping, follow existing regulations.
H = Difference in level between level in the tank and the pump axis.
L = Maximum length of suction pipe including the vertical lift. Subtract 0.25 mt.
for every bend or gate valve.
0006081470_201105
6 Suction pipe
7 Return pipe
8 Automatic fuel interception at burner shut off
9 One-way valve
8 Automatic fuel interception device at
burner shut off
9 One-way valve
10 Bottom valve
H
meters
0,5
1
1,5
2
2,5
3
3,5
11 / 28
H
Total length
metres
metres
Ø i. 16 mm.
1
40
1.5
45
2
45
2.5
50
3
50
H
Total length
metres
metres
Ø i. 16 mm.
1
40
1.5
45
2
45
2.5
50
3
50
Dimension P = 3.5 m. (max.)
Total length meters
Ø i. 14 mm.
Ø i. 16 mm.
36
55
30
48
25
41
20
32
15
24
10
15
4
7,5
E
N
G
L
I
S