General settings
Parameter
Description
System fluid
System fluid.
Select the used system fluid out of
the list by pressing the
corresponding radio button.
Boiler interlock
Boiler interlock settings.
External connections/interfaces
can be programmed to open when
pressure drops below or rises
above a critical boiler limit.
These limits can be set after
selecting the boiler interlock.
Common fault
General contact for errors
Contact is normally open (NO) by
default, but can be switched to
normally closed (NC).
Is the common fault set to
normally closed (NC), switching off
the mains power will make this
contact NO as long as the power is
switched off.
/i
Degassing settings
Parameter
Description
Auto degass time
Time setting for daily start time
1
and stop time of the degassing
process.
Auto degass time
Second time setting for daily start
2
time and stop time of the
degassing process.
Block time
Periods that the unit is not allowed
to degass.
17
Water
Water glycol mixture
Weekday (every day of the
week can be chosen)
Year (max. 5 periods per year
can be chosen)
/i
Refill settings (only for S400-R and S400-B versions)
Parameter
Refill volume
alarm after
Refill time alarm
after
Max. refill
frequency
/i
Parameter
Max. system
pressure
Desired operating
pressure
Refill pressure
English
Description
Maximum allowed refill quantity
per refill. Issues an alarm if a refill
exceeds this threshold.
Range: 0 - 2500 l; 0 = switched
off.
Maximum continuous refill time.
Range: 0 - 255 min.; 0 = switched
off.
Maximum number of times per
day that refilling is allowed
Range: 0 - 10 times; 0 = switched
off.
Pressure settings
Description
Pressure at which the unit stops
and triggers an alarm.
This pressure should be lower than
the system safety valve setting.
Drag the label to the desired
pressure
The preferred system pressure.
This is the pressure at which the
refilling stops.
Drag the label to the desired
pressure.
Only for S400-R and S400-B
versions.
The preferred system pressure at
which the refilling starts.
Set this value as low as possible
when the refilling is controlled by
an external refill system.
Drag the label to the desired
pressure.
Only for S400-R and S400-B
versions.
User manual - 1.0