1.
Drag the label of the maximum pressure (A) to the
desired maximum pressure.
2.
For units of -R and -B versions: Drag the label of
the operating pressure (B) to the desired operating
pressure.
3.
For units of -R and -B versions: Drag the label of
the refill pressure (C) to the desired refill pressure.
NOTE
The minimum operating pressure (D) cannot
be changed.
4.
Select the next page button ( > ).
Execute the functional test
1.
Push the start button to start the functional test.
The functional test only starts if the unit
meets the following conditions:
The deaeration tank is filled with
•
system fluid.
The measured pressure is above the
•
minimum pressure (0.8 bar).
For -B versions: the break tank is
•
filled with refill fluid.
2.
When the display shows that the test is completed
successfully, push the OK button and proceed to the
next step, refer to § 5.4.4. The display shows the
home screen and the status is standby.
NOTE
During the functional test, warnings and
faults can be triggered (refer to § 7.5). If
this happens, remedy the failure and start
the functional test again.
If it is not possible to remedy the failure at
the moment, abort the functional test and
remedy the failure later on. When the
failure is solved, check if the unit is
functioning properly. Refer to § 5.4.3.
5.4.3
Check the operation when the functional
test was aborted
1.
Go to the home screen.
2.
Push the menu button.
3.
Select Operating mode.
4.
Select Automatic mode.
5.
Push the button Degass start.
14
0
6.
Check the indication of the pressure gauge (A). This
should alternately display overpressure and
underpressure.
NOTE
The SmartSwitch will automatically turn
off the unit when the concentration of
dissolved gases has reached the minimum
level.
5.4.4
Finish the startup
1.
Close the valve (B) behind the pressure gauge (A).
English
A
B
A
User manual - 3.0