General - all types (S600, S600-R, S600-B)
Problem
W32
Pressure drop inlet too high
W33 / E33
Pressure drop inlet too low
W34
Smart switch problem
E36
Check valve problem
E37
Pressure too high, repeatedly
W38
Pressure increase too high
Only applicable to the systems with the refill functionality (S600-R, S600-B)
Problem
W10 / E10
Refill flow too low
W11 / E11
Refill valve open
W13
Refill: too often
W14
Refill: too long
W15
Refill: too much
W24
Low level break tank
User manual - 3.0
Possible cause
The inlet valve is closed
The inlet is (partly) blocked
The filter (13) is clogged
The outlet valve is closed
The outlet line is (partly) blocked
The solenoid valve (11) does not open Replace (part of) the solenoid valve.
The pump is not running
The SmartSwitch (3) is broken
Check the valve of the air outlet (5)
Incompressible system
Incompressible system
Possible cause
A valve in the refill inlet line is closed
The solenoid valve (24) does not open Replace (part of) the solenoid valve.
The refill line is blocked
The flow meter (26) is defective
The solenoid valve (24) of the refill
stays open
A leak in the system
Interaction with some expansion
systems
A leak in the system
Big installation
A leak in the system
Big installation
The inlet valve is closed
The inlet is blocked
The float valve is broken
English
Correction
Open the valve.
Remove the obstruction.
Clean the filter element.
Open the valve.
Remove the obstruction.
Check the pump and pump fuse.
Replace, if necessary. Refer to § 7.2.
Replace the Smart switch.
If necessary, replace the valve.
Check the expansion system.
Check the expansion system.
Correction
Open the valve.
Remove the obstruction.
Replace the flow meter.
Replace or clean (part of) the solenoid
valve.
Repair the leak.
Check the settings (max. freq. /
max. dp).
Repair the leak.
Check the settings Max. refill
time.
Repair the leak.
Check the settings Max. refill
volume.
Open the valve.
Check and clean the inlet.
Check or replace the float valve.