Machine Location

l
. The concrete floor must be of
Foundation
sufficient strength and thickness to handle the
floor loads generated by the high extract speeds
of the machine.
l
Service/Maintenance Space.
space to allow comfortable performance of
service procedures and routine preventive
maintenance.
This is especially important in connection with
machines equipped with an AC inverter drive.
Consult installation instructions for specific details.
&$87,21
Replace all panels that are removed to perform
service and maintenance procedures. Do not
operate the machine with missing guards or
with broken or missing parts. Do not bypass
any safety devices.

Input and Output Services

l
. Best performance will be
Water Pressure
realized if water is provided at a pressure of
30 – 85 psi (2.0 – 5.7 bar). Although the
machine will function properly at lower
pressure, increased fill times will occur. Water
pressure higher than 100 psi (6.7 bar) may
result in damage to machine plumbing.
Component failure(s) and personal injury could
result.
l
Steam Heat (Optional) Pressure.
performance will be realized if steam is
provided at a pressure of 30 – 80 psi (2.0 – 5.4
bar). Steam pressure higher than 125 psi (8.5
bar) may result in damage to steam components
and may cause personal injury.
8
Provide sufficient
SW019
Best
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
For machines equipped with optional steam
heat, install piping in accordance with approved
commercial steam practices. Failure to install
the supplied steam filter may void the warranty.
l
Drainage System.
troughs large enough to accommodate the total
number of gallons that could be dumped if all
machines on the site drained at the same time
from the highest attainable level. If troughs are
used, they should be covered to support light
foot traffic.
l
For personal safety and for proper
Power.
operation, the machine must be grounded in
accordance with state and local codes. The
ground connection must be to a proven earth
ground, not to conduit or water pipes. Do not
use fuses in place of the circuit breaker. An
easy-access cutoff switch should also be
provided.
:$51,1*
Ensure that a ground wire from a proven earth
ground is connected to the ground lug near the
input power block on this machine. Without
proper grounding, personal injury from electric
shock could occur and machine malfunctions
may be evident.
Always disconnect power and water supplies before
a service technician performs any service
procedure. Where applicable, steam and/or
compressed air supplies should also be
disconnected before service is performed.
Provide drain lines or
SW008
F232073