7.7

During operation

8

Shut-down/dismantling

8.1

Personnel qualifications

166
Shut-down/dismantling
DANGER
Risk of explosion due to overpressure in the hydraulics!
If the gate valves on the suction and pressure sides are closed during operation, the
fluid in the hydraulics housing is heated up by the pumping movement. This heating
creates a pressure of several bars in the hydraulics. The pressure can result in the
pump exploding! Make sure that all gate valves are open during operation. Open
closed gate valves immediately!
WARNING
Amputation of limbs due to rotating components!
No persons must be present in the work area of the pump! There is risk of (serious)
injuries due to rotating components! No persons must be present in the work area of
the pump during start-up or operation.
WARNING
Risk of burns from hot surfaces!
Motor housing can become hot during operation. It may cause burns. Allow the
pump to cool down at ambient temperature after switching it off!
NOTICE
Pumping problems due to water level being too low
The hydraulics are self-venting. Smaller air cushions are resorbed during pumping. If
the fluid is lowered too much, separation of the volume flow may occur. The min-
imum permissible water level must reach the upper edge of the hydraulics housing!
When operating the pump, observe the locally applicable regulations on the following
topics:
▪ Work safety
▪ Accident prevention
▪ Handling electrical machines
Strictly adhere to the responsibilities of the personnel specified by the operator. All
personnel are responsible for ensuring that the responsibilities of the personnel and the
regulations are observed!
Due to their design, centrifugal pumps have rotating parts that are easily accessible.
Depending on the operating condition, sharp edges can develop on these parts. WARN-
ING! This can lead to cuts and limbs may be amputated and severed! Check the fol-
lowing at regular intervals:
▪ Operating voltage (+/-10 % of the rated voltage)
▪ Frequency (+/-2 % of the rated frequency)
▪ Power consumption between individual phases (max. 5 %)
▪ Voltage difference between the individual phases (max. 1 %)
▪ Max. switching frequency
▪ Minimum water submersion depending on the operating mode
▪ Inlet: no air intake
▪ Level control device/dry-running protection: Switching points
▪ Quiet/low-vibration running
▪ All gate valves open
▪ Operation/control: Operating personnel must be instructed in the functioning of the
complete system.
▪ Electrical work: A qualified electrician must carry out the electrical work.
▪ Installation/dismantling: The technician must be trained in the use of the necessary
tools and fixation materials for the relevant construction site.