Connecting a timer or magnetic induction detector.
The contact is normally open. With DSW1 Dip switch 1 ON (automatic closing active) and DSW1 Dip switch 4 ON (collective function active), you
can connect a timer or a magnetic induction detector. Normally open input P.SEQ, if closed, operates the complete opening of the gate for as long as
the contact remains closed. The gate opens and remains open. Controls SEQ, PED and the remote controls stored are not active until the contact is
reopened. This input is used to open the gate and keep it open at the busiest hours. LED DL2 lights up and LED DL.S flashes when the timer or the
magnetic induction detector are operated.
Connecting photocells.
Observe the correct polarity for the photocell power supply. Contacts SCL and P.IN are normally closed.
The triggering of input SCL, during gate closing, inverts motion. If not used, jumper between COM and SCL. With the photocells not engaged, LED DL5
must be on.
The triggering of input P.IN, during gate closing, blocks motion until the photocells remain engaged; upon their disengagement, motion is inverted into
an opening of the gate. The triggering of input P.IN, during gate opening, blocks motion until the photocells remain engaged; upon their disengagement,
gate opening resumes. If not used, jumper between COM and P.IN. With the photocells not engaged, LED DL1 must be on.
Internal
photocell
TIMER
External
Internal
photocell
photocell
External
photocell
Safety device when closing N.C.
EN
Safety device when
opening and closing N.C.
Accessories +24VDC
Accessories -24VDC