A
NNEX
General overview and guide to start up the unit
Space heating
Temperature set point
start blinking
You selected remote
Yes
controller room
temperature
thermostat operation?
temperature
[8-00]=1, default
(page 24)
No
You selected multiple
Yes
set point control
operation pattern B
temperature
including remote room
thermostat controller
control?
[7-02]=1 and ([7-03]=1
or/and [7-04]=1)
(page 23)
Blank display
You selected
automatic leaving
water control
(page 22)
Shift value
▼
Floor heating
▼
ΔT: 5°C [A-02]
▼
Automatic leaving
No
water temperature?
Yes
▼
▼
Automatic leaving
35°C
water settings
[3-00]=–10
[3-01]=15
[3-02]=40
[3-03]=25
Installation manual
39
Push the
button
Room
Room
What type of appliance do you
have?
Push the
button
[A-03]
Water
or/and
temperature
[A-04]
Push
ON/OFF
What type of appliance do you have?
▼
Radiator
▼
Yes
High temperature?
▼
ΔT: 10°C [A-02]
default value
▼
Automatic leaving
No
water temperature?
Yes
▼
▼
Automatic leaving
65°C
water settings
[3-00]=–10
[3-01]=15
[3-02]=70
[3-03]=45
"
"
External room thermostat
temperature
External room thermostat
temperature
"
"
[A-03]
or/and
[A-04]
No
▼
ΔT: 5°C [A-02]
▼
Automatic leaving
No
water temperature?
Yes
▼
▼
Automatic leaving
50°C
water settings
[3-00]=–10
[3-01]=15
[3-02]=55
[3-03]=40
Yes
You selected leaving
water control operation
[8-00]=0 (page 24)
No
Yes You selected external
room thermostat
operation [6-01]=1
(page 23)
No
Yes You selected multiple
set point control
operation pattern B
including external room
thermostat
[7-02]=1 and ([7-03]=1
or/and [7-04]=1)
[6-01]=1 (page 23)
No
You selected
permission level 3 on
remote controller
[0-00]=3 (page 20)
Yes You selected multiple
set point control
operation pattern A
[7-02]=0 and ([7-03]=1
or/and [7-04]=1)
(page 23)
▼
Fan coil
▼
ΔT: 5°C [A-02]
▼
Automatic leaving
No
water temperature?
Yes
▼
▼
Automatic leaving
45°C
water settings
[3-00]=–10
[3-01]=15
[3-02]=50
[3-03]=35
RKHBRD011~016ABV1+Y1
Indoor unit for air to water heat pump system
4PW61218-1C – 2012.06