AHT Cooling Systems GmbH
►In event of damage, contact the
maintenance service (see → Chapter
10.5).
WARNING
Transport the device with floor trucks.
Risk of injury to persons during
collisions.
►Observe the transport routes for floor
trucks.
►Secure the cargo.
►Floor trucks must only be operated
by trained persons.
►Observe the details for the stacking
height on the packaging.
NOTE
• Material damage due to transport and storage.
►Do not expose the device during storage and
transport to temperatures higher than 70°C (158°F).
►Transport and store the device only in a type-based
stable operating position (horizontal alignment).
►If the device was still inclined during transport,
wait a minimum of 2 hours before commissioning.
►When being delivered, ensure continuous
accessibility up to the installation room. (Observe
the transit heights/widths/installation space height
and adequate shunting radii.)
6 Unpacking
Check the device for damage (bumps, scratches)
before and during unpacking. Contact the maintenance
service in case of damage (see → 10.5).
WARNING
Disposal of packaging material and
films. Danger of suffocation.
►Keep packaging material and foils
away from children.
►Do not let children play with them.
WARNING
For devices of type R-290: Damage to the
refrigerant circuit. The refrigerant can
escape and create an explosive gas/air
mixture. Risk of fire.
►Ensure good ventilation.
►Observe the safety and warning
information for devices with flammable
refrigerants (see → Chapter 1.6.2.1).
►In event of damage, contact the
maintenance service (see → Chapter
10.5).
Heavy device parts. Hands can be
jammed.
►When unpacking, pay attention to
fingers and hands.
►Wear protective gloves.
on18.05.2018 11:08
CAUTION
361929_0917_BA_SM_V4_06.09.2017_U_enUS_DRUCK.docx
NOTE
• Material and property damage due to missing
parts of the device.
►Check for loose parts in the packaging. ►Do not
dispose of loose parts. If it cannot be determined
where the loose parts belong, check with the
maintenance service (see→ Chapter 10.5).
7 Setup and installation
The operating company can set up and install the device.
For technical data for interfaces, see → 2.2.
Technical modifications to the device can only occur
with the coordination and approval of the
manufacturer.
NOTE
Material and property damage due to congestion of
•
the warm exhaust air (heat accumulation).
►The exhaust air must be able to escape freely to
the rear side.
►Minimum distance with separate installation
All round: 100 mm
►Minimum distance with block installation (see → Fig. 5.)
A= 0 mm
B= 100 mm / 155 mm (device-specific)
Fig. 5: Minimum distances with block installation
►
With the block installation, the ventilation openings
on the device cover must not be blocked.
►Superstructures can be attached only in agreement
with the manufacturer.
Minimum distance 100 mm.
The devices may be connected using bus cables (see
→ Chapter 4.2.2.3, 4.2.3.3).
The temperature display, safety instructions and
power rating plate (see → Chapter 2.2.1) must
always be kept clear.
WARNING
Danger of tilting of the device. People's
bodies can be jammed.
►Remove the transport pallet only when the
stable, final installation position has been
reached. If you have questions, contact the
maintenance service (see → Chapter 10.5).
►Do not climb onto or into the device.
Page 46