External voltage supply
)
Note!
Always use a separate power supply unit in every control cabinet and safely
separate it according to EN 61800−5−1 ("SELV"/"PELV") in the case of external
voltage supply and larger distances between the control cabinets.
ƒ The external voltage supply of the communication module is required if
communication is to continue when the power supply of the standard device fails.
ƒ Access to parameters of a standard device disconnected from the mains is not
possible.
ƒ The external voltage supply is effected via the 2−pole plug connector.
Assignment of the 2−pole plug connector (X200)
Designation
+
−
Terminal data
Area
Electrical connection
Possible connections
Tightening torque
Stripping length
EDK94AYCPM DE/EN/FR/ES/IT 6.1
Description
U = 24 V DC (20.4 V − 0 % ... 28.8 V + 0 %)
I = 130 mA
Reference potential for external voltage supply
Values
Plug connector with screw connection
rigid:
flexible:
0.5 ... 0.6 Nm (4.4 ... 5.3 lb−in)
6 mm
l
Electrical installation
External voltage supply
2
1.5 mm
(AWG 16)
without wire end ferrule
2
1.5 mm
(AWG 16)
with wire end ferrule, without plastic sleeve
2
1.5 mm
(AWG 16)
with wire end ferrule, with plastic sleeve
2
1.5 mm
(AWG 16)
6
43