Diagnostics; Led Status Displays - Lenze E94AYCPM Instrucciones Para El Montaje

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

8

Diagnostics

LED status displays

LED
Pos.
Colour
MS
Green
ME
Red
BS
Green
BE
Red
DE
Red
EDK94AYCPM DE/EN/FR/ES/IT 6.1
Condition
Description
On
The communication module is supplied with voltage and
connected to the standard device.
Blinking
The communication module is supplied with voltage, but has no
connection to the standard device. (The standard device is
switched off, initialising, or not present.)
On
An error in the communication module has occurred.
Blinking
Communication via the communication module has been
established. PROFIBUS communication is active.
On
Bus monitoring has been triggered.
On
The communication module is not accepted by the standard
device. (See notes in the documentation for the standard device.)
l
Diagnostics
LED status displays
E94YCIB001F
8