Connection of the storage system
8. Connection of the storage system
This chapter explains the requirements and process for connecting the storage system wiring to the unit. Read
carefully before starting the connection process.
8.1. Safety instructions for connecting the storage system
Before you start to make the connections, make sure there is no voltage in the inverter. Check that
the AC protection of the auxiliary grid/genset and the DC switch are open.
Do not switch on the power to the unit until you have successfully made the rest of the connections
and the unit is closed.
8.2. Wiring requirements for connecting the storage system
The wiring gauge for connecting the storage system is specified in the following table:
Storage system wiring gauge
Cable diameter
8.3. Storage system connection process
To connect the storage system:
1.
Loosen the packing gland marked BATTERY + (see section "2.7. Description of wiring inlets"), remove the
protective cap and pass the positive pole cable through it. Ingeteam recommends using a tubular terminal in
accordance with DIN 46 228/1.
2.
Open the clamp-type terminal J50 BATTERY +, insert the cable and close the terminal.
3.
Loosen the packing gland marked BATTERY -, remove the protective cap and pass the positive pole cable
through it. Ingeteam recommends using a tubular terminal in accordance with DIN 46 228/1.
4.
Open the clamp-type terminal J51 BATTERY +, insert the cable and close the terminal.
5.
Correctly tighten the packing glands to prevent losses to the protection class, verifying that the wiring is
not taut. Check that the connection is tight.
ABH2013IQM01_A - Installation and Operation Manual
INGECON SUN STORAGE 1Play
10 ~ 16 mm
2
7 ~ 13 mm
Ingeteam
DE
EN
ES
FR
IT
PT