COMBUSTION
During combustion in NORMAL status, the system can pass to MODULATION if:
• the smoke temperature exceeds the optimal value of the operating condition.
• or the temperature of the water in the boiler exceeds the value of the thermostat set.
MODULATION has the purpose of reducing combustion to gradually reach the water thermostat
value set or lower the smoke temperature. Modulation brings the system to power 1.
During combustion in NORMAL status, the system can pass to SWITCH OFF if:
• the smoke temperature goes below 50°C;
• the smoke temperature for each operating power goes below the minimum threshold.
During combustion, the system can go to SWITCH OFF and SAFE status if:
• the smoke temperature exceeds the factory threshold set.
• the boiler water temperature exceeds 85°C.
During combustion, the system can go to STAND-BY status if:
• the buffer temperature is over the SET temperature for 2 minutes.
On pressing the
This phase has the purpose of bringing the smoke temperature under the value of the boiler off
50°C, once complete the system cleans the crucible and the exchangers and then goes to OFF
status.
LOCK STATUS
This status is present during boiler operation or also with the system off if one of the errors among
those described on page 68 occurs.
To reset the system lock status, you need to:
• solve the error that occurred (e.g. safety thermostat activation on boiler temperature reset).
• if the alarms are no longer present, press the
OFF.
INSTRUCTIONS FOR USE
key, the boiler in whatever status, goes to SWITCH OFF.
Friday 15:29
Switch off
Friday 16:23
Block
key for 3 seconds and the system switches
- 79
-