MENU P6 – PROGRAMMABLE OUTPUTS
PAR
Function
P6.1.1
Function of prog. output 1
terminal 4.1
P6.1.2
Prog. output 1 mode
P6.2.1
Function of prog. output 2
terminal 4.3
P6.2.2
Prog. output 2 mode
P6.3.1
Function of prog. output 3
terminal 5.1
P6.3.2
Prog. output 3 mode
P6.4.1
Function of prog. output 4
terminal 5.3
P6.4.2
Prog. output 4 mode
P6.5.1
Function of prog. output 5
terminal 3.1
P6.5.2
Prog. output 5 mode
P6.6.1
Function of prog. output 6
terminals 3.3-3.4
P6.6.2
Prog. output 6 mode
Functions of Programmable Outputs
COD
Function
OFF
Output not used
OP.1
Line 1 circuit breaker open control (Open 1)
Contact which closes to command the opening of line 1 circuit breaker. It may remain energized or be released when the operation
is completed, depending on P2.07 setting. (not used when contactors or switches are used)
CL.1
Line 1 circuit breaker close control (Close 1)
Contact which closes to command the closing of line 1 circuit breaker. It may remain energized or be released when the operation
is completed, depending on P2.07 setting
OP.2
Line 2 circuit breaker open control (Open 2)
Like OP.1, referred to line 2
CL.2
Line 2 circuit breaker close control (Close 2)
Like CL.1, referred to line 2
OP.A
Open control for both lines (Open All)
Used to set motorised switches to neutral position, with both lines open
GC.2
Generator Control 2
Start / stop control for the generator connected to line 2. When closed it commands the shutdown of the generator set.
Used in Utilty-Generator applications
RDY
ATL10 Ready
It signals that the unit is in automatic mode and without alarms, ready for intervention
ALA
Global Alarm
Energized output under standard conditions, de-energized in the presence of any alarm
L1.S
Line 1 Status
The output is energized when there are all the conditions to connect load to line 1
L2.S
Line 2 Status
The output is energized when there are all the conditions to connect load to line 2
P6.x.2 – Set the output status when the selected function is not active.
dir = not energized, rev = energized
MENU P7 – SERIAL COMMUNICATION
PAR
Function
P7.01
RS-232 Address
P7.02
RS-232 Baud Rate
P7.03
RS-232 Protocol
P7.04
RS-232 Parity
P7.01...P7.04 – Define the transmission format and the protocol used on the RS-232 communication port.
Range
Default
See list
OP.1
Nor/Inv
Nor
See list
CL.1
Nor/Inv
Nor
See list
OP.2
Nor/Inv
Nor
See list
CL.2
Nor/Inv
Nor
See list
rdy
Nor/Inv
Nor
See list
GC.2
Nor/Inv
Nor
Range
Default
1 ..245
1
2400
9600
4800
baud
9600
19200
38400
RTU – Modbus RTU
RTU
ASC – Modbus ASCII
NONE – None
NONE
ODD - Odd
EVEN- Even
G
B
9