d
Sensor DIP Switch Settings
IR CM / DT CM
DIP 1
Normal mode / Test mode (NORM / TEST)
Test mode has priority over all
ambient light level, the presence
other settings on the presence
detector activates the light to stay
detector and serves the purpose
'ON' for approx. 8 sec. in response
of checking for proper working
to movement in the room (blue
order as well for testing the
LED flashes when movement is
detection zone. Irrespective of
detected). All user-selected
DIP 2
Manual ON mode (MAN) / Automatic mode (AUTO)
Manual ON mode: (MAN)
The load will only switch 'OFF'
Light is switched 'ON' manually by
automatically.
the occupant and stays 'ON' for
Automatic mode: (AUTO)
The light automatically switches
at any time. When switched 'OFF'
'ON' and 'OFF' in relation to
manually this temporarily
occupancy and daylight
interrupts the
contribution. Light can be
automatic 'ON' function as long
switched 'ON' and 'OFF' manually
as the room is occupied. Once
DIP 3
Momentary / Maintained switch option
Tells the sensor how to interpret
as a manual on unit or override it
the incoming maintained or
manually at any time. When using
momentary switching signal.
the IR CM DIM-24 or DT CM DIM-
Assigning external (momentary)
24 and a momentary switch, light
buttons / (maintained) switches
can be dimmed manually by
allows you to operate the detector
pressing and holding the
DIP 4
'ON' only / 'ON'&'OFF' manual switching
In the 'ON'-'OFF' setting, the light
pulse mode: no manual 'OFF').
can be switched 'ON' and 'OFF'
In the 'ON' setting, light can not
manually at any time (except in
be switched 'OFF' manually.
potentiometer settings apply in
normal mode. The presence
detector can also be set by means
of the LEDs without any load
connected.
the time
setting of the sensor.
the room is no longer occupied
and the time delay of the sensor
has elapsed, the sensor will return
to the automatic 'ON' function.
momentary switch until the
desired light level is achieved.
Maximum wire length between
sensor and switch <50 m / 164 ft.
The stay-'ON' time starts from the
beginning again each time the
button is pressed.
- 18 -
d
Sensor DIP Switch Settings
DIM-24
DIP 5
Constant light level DIM control option ON / OFF
If activated, the presence detector
The lights can be manually
provides constant light level. The
controlled by the end user with
detector measures the level of
either the RC 4 remote control or a
daylight and activates sufficient
momentary switch (ON / OFF /
artificial light to achieve the
Dim UP / Dim Down). Pressing and
required level of light intensity. As
holding the momentary switch
daylight changes, the electric light
will dim UP / Down, momentarily
is adjusted accordingly. If
pressing the switch will turn the
deactivated, the detector switches
lights ON/OFF.
artificial light on with the last set
light intensity by pushbutton or
When constant lighting control is
remote control RC 4 (factory
enabled, the electric light level is
setting 100%.) In addition to the
constantly adjusted in relation to
daylight component, electric light
the daylight contribution in the
is also switched 'ON' and 'OFF' in
space to maintain a constant level
relation to whether or not persons
of lighting (daylight + electric
are present.
light.) Upon occupancy the light is
turned ON and immediately starts
dimming to the last selected light
level (daylight + electric light.)
When constant lighting control is
disabled, the electric light level is
not adjusted in relation to daylight
contribution. The dim level is only
selected by the RC 4 remote
control or a momentary switch.
Upon occupancy the light is
immediately turned ON to the last
selected dim level.
- 19 -