4.7.2

Transistor Output (Source or "+" Common Only) Wiring Diagram

ENG
%
&
Volt
5
12-24
5,12,24
+
'
)
(
+
OUT1
OUT2
$
#
+
Output Terminal Notes
Each circuit can contain from one output terminal up to every output terminal.
Each circuit can contain from one output terminal up to every output terminal.
Using any combination of 5 Volt, 12 Volt, and 24 Volt outputs can be accomplished on the same
α
Series Controller if separate circuits are used for each voltage level.
!
"
OUT3
OUT4
$
%
#
#
+
&
Table 4.5: Transistor Output Wiring
Ref.
Item Description
α
1
Base Unit
2
Output Terminals
3
Output Devices
Circuit Protection Device - See
4
Table 4.6 for Specifications
5
Emergency Stop
6
DC Power Supply for output
7
Power Terminal
8
DC Power Supply, 24V DC
Circuit Protection Device
9
- Limit to 1.0 Amps
Table 4.6: Transistor Output Circuit
Protection Table
Circuit Voltage Circuit Protection (Fuse)
5 Volt
< 0.3 Amps per Circuit
12 Volt
< 2.0 Amps per Circuit
24 Volt
< 2.0 Amps per Circuit