Connect the oven to the gas line with the proper
type of gas according to Local and National In-
stallation Standards.
SG2136 series ovens are rated at 60,000 BTU/Hr
(17.6 kW) (63 MJ). Each oven has been adjusted
at the factory to operate with the type of gas speci-
fied on the rating plate attached to the left side of
the control panel.
Each oven is supplied with a regulator to maintain
the proper gas pressure. The regulator is essen-
tial to the proper operation of the oven and
should not be removed or replaced with
another model unless approved by Blodgett.
DO NOT INSTALL AN ADDITIONAL REGULATOR
WHERE THE OVEN CONNECTS TO THE GAS
Type of
Inlet
Gas
Pressure
mbars
G20
25
G25
20
G20/G25
G20/G25
20/25
20/25
G30
30/50
G31
30/37/50
NOTE: * Use with pre-injector of 3.52 mm.
Burner
Pressure
mbars
8.7
13
Totally Inscrewed
Totally Inscrewed
Pressure Regulator
20
25
19
Installation
SUPPLY UNLESS THE SUPPLY EXCEEDS THE
MAXIMUM.
The oven and its individual shutoff valve must be
disconnected from the gas supply piping system
during any pressure testing of that system at test
pressures in excess of 1/2 psig (3.45kPa).
The oven must be isolated from the gas supply
piping system by closing its individual manual
shutoff valve during any pressure testing of the
gas piping system at test pressures equal or less
than 1/2 psig (3.45kPa).
Setting Equipment for Other Types of Gas
Contact a qualified service agency to convert to
another type of gas.
Injector
Air
Diameter
Opening
mm
mm
2.45
2 x 16
2.45
2 x 16
2.45
2.45*
2 x 16
2 x 16
2.08
2 x 16
2.08
2 x 16

Gas Connection

Pilot
Standard
Injector
Delivery
mm
Value kW (H
2 x 0,63
17,6 Nat. Gas
2 x 0,63
17,6 Nat. Gas
2 x 0,63
2 x 0,63
17,6 Nat. Gas
17,6 Nat. Gas
2 x 0,30
17,6 Butane
2 x 0,30
17,6 Propane
)