Connecting Up Flue - Sime Format Instrucciones Para El Instalador

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

2.3. 1
Filter on the gas pipe
The gas valve is supplied ex factory with an
inlet filter, which, however, is not adequate
to entrap all the impurities in the gas or in
gas main pipes.
To prevent malfunctioning of the valve, or in
certain cases even to cut out the safety
device with which the valve is equipped,
install an adequate filter on the gas pipe.
2.4
CHARACTERISTICS
OF FEEDWATER
To prevent lime scale and damage to the
tap water exchanger, the water supplied
should have a hardness of no more than
20°F. In all cases the water used should be
tested and adequate treatment devices
should be installed. To prevent lime scale or
deposits on the primary exchanger, the
water used to supply the heating circuit
should must be treated in accordance with
UNI-CTI 8065 standards.
It is absolutely essential that the water is to
be treated in the following cases:
– very extensive system (with high con-
tents of feedwater);
– frequent addition of makeup water into
the system;
– should it be necessary to empty the
system either partially or totally.
2.5
SYSTEM FILLING
Filling of the boiler and the system is done
by the charge cock on the divertor valve (2
fig. 7). The charge pressure, with the
system cold, must be between 1 and 1.2
bar. During system filling you are recom-
mended to keep the main switch turned
OFF. Filling must be done slowly so as to
allow any air bubbles to be bled off through
the air valves. Should the pressure have
risen well above the limit expected, dischar-
ge the over pressure by opening the pres-
sure-relief valve (9 fig. 7).
2.6
FLUE
The flue for the atmospherical expulsion of
the combustion products from natural
draught appliances must meet the following
requirements:
– Be gas-tight to the combustion products,
waterproof and thermally insulated.
– Be built of materials suitable for keep
resisting to normal mechanical stresses,
heat, and the action of combustion pro-
ducts and their possible condensates.
– Follow a vertical path and not present
any throttling throughout its entire
length.
– Be adequately insulated to prevent phe-
nomena of condensation or smokes coo-
ling, in particular if located outside the
building or in unheated ambiences.
– Be set at an adequate distance from
5
7
1
2 3
combustible or easily inflammable mate-
rial by means of an air gap or suitable
insulating material.
– Have beneath the mouth of the first
smoke duct a chamber for collecting
solid material and any condensate; the
height of the chamber must be at least
500 mm.
Access to the chamber must be guaran-
teed by means of an opening provided
with an air-tight metal door.
– Have a circular, square, or rectangular
internal cross section; in the case of
square or rectangular sections, the cor-
ners must be rounded off with a radius
of no t less t han 20 mm. However,
hydraulically equivalent cross sections
are allowed.
– Be equipped with a chimney-pot at the
top, which must be outside the so-called
back-flow zone, so as to prevent the for-
mation of back-flow, which prevents free
discharge of the products of combustion
into the atmosphere.
– Be devoid of mechanical means of suc-
tion located at the top of the pipe.
– No overpressure should be present in a
chimney that passes within or close up
to inhabited rooms.
2.6. 1

Connecting up flue

Fig. 8 refers to the connection of the boiler
"25 OF - 30 OF" to the flue or chimney
through smoke ducts. When making the
connection, in addition to respecting the
dimensions given, you are recommended
to use gas-tight materials capable of resi-
sting over time mechanical stresses and
the smokes heat.
At any point along the smoke duct, the tem-
perature of the combustion products must
be higher than the dew point. More than a
total of three changes of direction must not
be made, including the inlet connection to
the chimney/flue.
For any changes of direction use only cur-
ved pipe lengths.
Fig. 8/a shows some applications of drau-
ght terminals that ensure proper expulsion
of the combustion products, in case of
discharge through the wall.
KEY
6
1 D.H.W. inlet-
outlet manifold
2 Filling cock
9
3 D.H.W. filter
4 Manifold by-pass
5 Water rate adjuster
6 D.H.W. exchager
7 Microswitches
8 Water pressure switch
9 Pressure-relief valve
4
8
2.7
"25 BF - 30 BF"
COAXIAL DUCT
The air inlet-smoke outlet assembly ø
60/100 is supplied in a kit code 8084805
complete with mounting instructions.
Fig. 7
Fig. 8
Fig. 8/a
77