Preparation for installing the unit

5.2. Environmental conditions

Environmental operating conditions indicated in the specifications table must be taken into account when choosing
the location of the unit.
The surrounding atmosphere must be clean and at temperatures above 40 ºC, the relative humidity must be
between 4% and 50%. Higher percentages of relative humidity up to 95 % are tolerated at temperatures below
30 ºC.
It should be borne in mind that moderate condensation may occasionally occur as a consequence of temperature
variations. For this reason, apart from the unit's own protection, it is necessary to monitor these units once they
have been started up on sites where the conditions described above are not expected to be present.
In the event of condensation, never apply voltage to the unit.

5.3. Supporting Surface and Fastening

To guarantee good heat evacuation and promote sealing, the units must be placed on a perfectly vertical wall or,
failing this, with a slight slope of a maximum of +80° or -80°.
Reserve a solid wall to which to attach the unit. It must be possible to drill the wall and fit suitable wall anchors
and self-tapping screws to support the unit's weight.

5.4. Critical load connection protection

Thermomagnetic circuit breaker
A thermomagnetic circuit breaker must be installed in the critical load output.
The following table provides the necessary data for the selection of these devices by the installer.
INGECON SUN STORAGE 1PLAY TL M
3TL M
6TL M
You must take into account when selecting the protection that the ambient working temperature influences the
maximum current permitted by these protections as indicated by the manufacturer.

5.5. Protection of the connection to the auxiliary grid/genset

Thermomagnetic circuit breaker
A thermomagnetic circuit breaker must be installed on the connection from the inverter to the auxiliary grid/genset.
ABH2014IQM01_A - Installation and Operation Manual
Maximum current
13 Arms
26 Arms
Ingeteam
Thermomagnetic circuit breaker
rated current
20 Arms
32 Arms
EN
ES
FR
PT