18.11. Inverter power limitation reasons

On occasion the inverter may reduce the AC output power due to different reasons. In the event that the unit is
connected to a grid or auxiliary generator and there is a reduction in power, the most restrictive reason for power
limitation is shown.
The various reasons for limiting the power are explained below.
Reason
communications
Battery Power Limited
Self Consumption
AC Grid Power Limited
Pac vs Fac Algorithm
Soft Start
High Bus Voltage
Protection
LVRT or HVRT Process
Charge Power
Configured
Grid Consumption
Protection
PV Surplus Injected to
the Grid
Nominal AC Current
PV Surplus Injected to
the Loads
Temperature
Pac vs Vac Algorithm
Communication

18.12. Automatic battery emergency charge

An emergency charge must be performed when the installation is stopped due to a total battery discharge.
This function allows to charge the batteries up to a certain level in order to have enough energy to restore the
system again.
For the unit to carry out an emergency charge, the batteries must be in one of the following states:
Low charge level, SOC <= SOCdescx. (Code3 "Low Battery SOC Descx").
Low voltage, Vbat <= Vmin. (Code2 "Low Battery Vmin").
In Li-Ion batteries, when the BMS requires a forced charge due to the battery being totally discharged.
The inverters can charge the batteries from different energy sources. Depending on the energy source available,
this emergency charge will be automatically activated by the inverter.
56
Reasons for the power limitation
Code sent by
9
Batteries. Limitation due to the storage system state of charge or configuration.
11
Self consumption mode. Limitation due to self consumption mode running.
Power available Battery charge limitation from the grid/genset due to the power
available. This power is calculated with the rated power in the case of the
10
generator, or the contracted power in the case of the grid, minus the power
Grid frequency. Limitation due to the grid frequency variation. Applicable
4
Initial connection ramp. Limitation after a grid reconnection. Applicable
5
12
Grid voltage drops. Limitation due to voltage drops in the grid. Applicable
13
Configuration. Battery charge limitation from the grid/genset, defined by a user
6
Grid consumption. Limitation due to the power consumption from the grid, when
15
working without batteries (only PV array) or when the batteries cannot absorb
Photovoltaic excess. Limitation of the injection of photovoltaic excess to the grid
16
14
Apparent power. Limitation due to rated apparent power in the unit.
Limitation of the injection of photovoltaic excess to the loads due to the operation
7
2, 3
Grid voltage. Limitation due to the grid voltage variation. Applicable according to
8
1
Description
consumed by the charges.
according to selected regulations.
according to selected regulations.
DC bus. Limitation due to high voltage in the internal DC bus.
according to selected regulations.
setting.
energy.
by configuration.
of the UPS or stand-alone modes.
Temperature. Limitation due to high temperature in the unit.
selected regulations.
Limitation caused by setpoint sent through communications.
ABH2014IQM01_A- Installation and Operation Manual