Technical characteristics
Output rating
AC-input power
Voltage
Frequency
Output power (operation
on battery power)
Voltage
Frequency
Battery
Environment
Noise level (operation on
AC-input power)
Operating temperature
Relative humidity
(1) Above 184 V on normal utility power. Below this value, the level of output power is lower.
(2) The upper and lower thresholds may be set using the UPS Driver software.
(3) Or 40 Hz in low-sensitivity mode (may be set using the UPS Driver software).
(4) Adjustable from 200 to 240 V using the UPS Driver software.
Pulsar Evolution 2200
(1)
2200 VA / 1540 W
Single-phase, 160 V to 294 V
47 Hz to 70 Hz (50 Hz system) or 56.5 Hz to 70 Hz
Single-phase, 230 V
6 x 12 V, 7 Ah, sealed lead-
acid, maintenance free
20 to 90% (without condensation)
6. Appendices
Pulsar Evolution 3000
3000 VA / 2000 W
(2)
(4)
(+ 6% / - 10%)
50/60 Hz +/- 0,1 Hz
6 x 12 V, 9 Ah, sealed
lead-acid, maintenance free
<40 dBA
0 to 40° C
Pulsar Evolution 3000 XL
3000 VA / 2000 W
(3)
(60 Hz system)
external
- Page 25
34007115EN/AA