Important Safety Instructions
Category III - 1000-Volt measuring instruments must be used for checking for the absence of voltage.
Ingeteam accepts no liability for any damages caused by improper use of the unit. You must propose
in advance to Ingeteam any work carried out on any equipment which implies a modification of the
original electrical arrangements. These must be studied and approved by Ingeteam.
Potential hazards for people
The equipment may remain charged after disconnecting the renewable power supply.
Carefully follow the mandatory steps in the manual for removing the voltage.
Always follow the indications in the manual on moving and placing the unit.
The weight of this unit can cause injury if not handled correctly.
Potential hazards for the equipment
After all duly authorized handling, check that the inverter is ready to start operation. Only after this
can you connect it, following the instructions in the manual.
Do not touch boards or electronic components. The more sensitive components can be damaged or
destroyed by static electricity.
Do not disconnect or connect any terminal while the unit is operating. Disconnect and check for
absence of voltage first.
Personal Protective Equipment (PPE)
When working on the unit, use the following safety equipment recommended by Ingeteam as a minimum.
Name
Safety footwear
Helmet with face shield
Working clothes
Dielectric gloves
Tools and / or equipment used in live work must have at least Category III-1000 Volts insulation.
Should the country's regulations demand another kind of personal protection, you should appropriately supplement
the equipment recommended by Ingeteam.
ABP2011IQM01_ - Installation and Operation Manual
In compliance with standard UNE-EN-ISO 20345:2012
In compliance with standard UNE-EN 397:1995, provided there are elements
with directly accessible voltage.
Close-fitting, non-flammable, 100% cotton
In compliance with standard EN 60903:2005