Preparation for installing the unit

6.3. Supporting Surface and Fastening

These inverters must be installed in accordance with the specifications in the following figure. The minimum
positive or negative inclination permitted will be 85º in relation to horizontal.
Reserve a solid wall to which to attach the unit. It must be possible to drill the wall and fit suitable wall anchors
and self-tapping screws to support the unit's weight.
The wall or support on which the unit is installed must be fireproof, as smooth as possible and sufficiently solid to
support the weight. Make sure that it supports at least twice the unit´s weight.
Conductive dust inside the unit may cause damage or problematic operations.
Make sure that the dust from drilling holes does not enter the equipment during installation.
We do not recommend fastening equipment with rivets or spot welding. However, if requiring a
weld, make sure the return wire is properly connected to not damage the equipment´s electronic
equipment. Furthermore, avoid inhaling the smoke from any welding operation.