Descripciones de parámetros
3.19.2 21-1* Ref. lazo cerrado 1/
Realimentación
3
3
Ilustración 3.49 Ref. lazo cerrado 1/Realimentación
21-10 Ref./Unidad realim. 1 Ext.
Option:
[0]
None
[1]
%
*
[5]
PPM
[10]
1/min
[11]
RPM
[12]
PULSO/s
[20]
l/s
[21]
l/min
[22]
l/h
[23]
m³/s
[24]
m³/min
[25]
m³/h
[30]
kg/s
[31]
kg/min
[32]
kg/h
[33]
t/min
[34]
t/h
[40]
m/s
[41]
m/min
[45]
m
[60]
°C
[70]
mbar
[71]
bar
[72]
Pa
[73]
kPa
[74]
m WG
168
®
VLT
Función:
Seleccionar la unidad para la referencia y la
realimentación.
Danfoss A/S © 10/2015 Reservados todos los derechos.
HVAC Drive FC 102
21-10 Ref./Unidad realim. 1 Ext.
Option:
[75]
mm Hg
[80]
kW
[120] GPM
[121] gal/s
[122] gal/min
[123] gal/h
[124] CFM
[125] ft³/s
[126] ft³/min
[127] ft³/h
[130] lb/s
[131] lb/min
[132] lb/h
[140] pies/s
[141] ft/m
[145] pies
[160] °F
[170] psi
[171] libras/pulg.²
[172] in wg
[173] pies WG
[174] pulg Hg
[180] CV
21-11 Referencia mínima 1 Ext.
Range:
0 ExtPID1Unit
*
21-12 Referencia máxima 1 Ext.
Range:
100
ExtPID1Unit
*
Función:
Función:
[ -999999.999 - par.
Seleccionar la referencia
21-12 ExtPID1Unit]
mínima para el
controlador de lazo
cerrado 1.
Función:
AVISO!
[ par. 21-11
- 999999.999
Ajuste el valor para el
ExtPID1Unit]
parámetro 21-12 Referencia
máxima 1 Ext. antes de ajustar
los valores del controlador PID
en el grupo de parámetros
20-9* Controlador PID.
Seleccione la referencia máxima
para el controlador de lazo cerrado
1.
La dinámica del controlador PID
depende del valor ajustado en este
parámetro. Consulte también el
parámetro 21-21 Ganancia propor-
cional 1 Ext..
MG11CE05