6.6.12 AE: Enabling the anti-blocking function

This function serves to avoid mechanical blockages in the event of prolonged disuses; it acts by periodically
activating the pump in rotation.
When this function is enabled, every 23 hours the pump complete an unblocking cycle lasting 1 minute.
6.6.13 Setup of auxiliary digital inputs IN1, IN2, IN3, IN4
This section shows the functions and possible configurations of the inputs by means of parameters I1, I2, I3,
I4. For electrical connections, see section 2.2.4.2.
The inputs are all the same and all functions can be associated with each. The parameter IN1..IN4 enables
the user to associate the required function with the input of the same name.
Each function associated with the inputs is explained in more detail further in this section.
Table 22 summarises the functions and various configurations.
The default settings are those in Table 21.
Value
Function associated with general input i
0
Input functions disabled
1
Water failure from external float (NO)
2
Water failure from external float (NC)
3
Auxiliary setpoint Pi (NO) related to input used
4
Auxiliary setpoint Pi (NC) related to input used
General enable of the inverter from external signal
5
(NO)
General enable of the inverter from external signal
6
(NC)
General enable of the inverter from external signal
7
(NO) + Reset of resettable blocks
General enable of the inverter from external signal
8
(NC) + Reset of resettable blocks
9
Reset of resettable blocks NO
Low pressure signal input NO, automatic and
10
manual reset
Low pressure signal input NC, automatic and
11
manual reset
12
NO low pressure input, manual reset only
13
NC low pressure input, manual reset only
ENGLISH
Default settings of inputs
IN1, IN2, IN3, IN4
Input
1
1 (float NO)
2
3 (P aux NO)
3
5 (enable NO)
4
10 (low pressure NO)

Table 21: Default settings of inputs

Summary of possible configurations of digital
inputs IN1, IN2, IN3, IN4 and relative operation

Table 22: Input configuration

120
Value
Display of active function associated
with input
F1
F1
F2
F2
F3
F3
F3
F3
F4
F4
F4
F4