Determine if the power track infeed housing
will be placed outside of the wall, inside of the
wall, or in the floor above a flush mounted
junction box.
(FOR INSIDE WALL OR OUTSIDE
WALL MOUNTING)
2.
Inspect the power track infeed housing for
damage. If it is damaged, the power track
infeed must be replaced (2a). The electrician
removes the two (2) T20 torx drive screws
holding the upper housing to the lower
housing (2b). Select a standard fitting (not
supplied by Steelcase) that best suits how the
incoming power is fed into the system (2c).
NOTE: For this example, a standard conduit
fitting has been installed in the upper housing
hole. The nut that comes with the conduit
fitting is tightened to secure it to the upper
housing. Reinstall the upper housing to the
lower housing with the two (2) T20 torx drive
screws that were removed in step 2b (2d).
For a floor infeed, stop at step 2a.
OUTSIDE OF WALL MOUNTING
(DRYWALL & V.I.A. SYSTEM)
POWER TRACK INFEED HOUSING
DAMAGE
2a
1
UPPER
HOUSING
LOWER
HOUSING
2b
1/2" CONDUIT
(NOT SUPPLIED
BY STEELCASE)
WALL
FLOOR
COVERING
INSIDE OF WALL MOUNTING
SEE NOTE
2c
2d
Page 7 of 75
24207101 Rev G