Configuring Remotely Controlled Adjustment Of Reactive Output Power Level - SMA PLA Option FLX Serie Guia De Instalacion

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Setup
2.1.2 Configuring Remotely Controlled
Adjustment of Reactive Output Power
Level
To configure the remotely controlled Power Level
Adjustment, choose the 'Reactive power' submenu.
2
2
Set the 'Remotely controlled reactive power (Q)'
radio button.
Configure the relay states (K1–K6) according to
the requirements of the DNO by entering the
Illustration 2.3 Configuring Reactive Power Control
10
appropriate reactive power setpoint of Q for each
relay state specified by the DNO. The value
entered is set on each inverter and represents the
amount of reactive power that the inverter will
deliver.
Leave Q settle time at 10 s, unless otherwise
specified by the DNO.
NOTICE
Q values can also be entered as absolute values by
changing the unit using the drop-down box.
L00410649-02_2q / Rev. date: 2014-06-20