Installation; Selection Of The Best Location - Friedrich DUCTLESS Manual De Instalación

Ocultar thumbs Ver también para DUCTLESS:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

INSTALLATION

Selection of the best location

Indoor unit
Install the air conditioner in the location that
satisfies the following conditions.
- The place shall easily bear a load exceeding
four times the indoor unit's weight.
- The place shall be able to inspect the unit as
the figure.
- The place where the unit shall be leveled.
- The place shall easily connect with the out-
door unit.
- The place where the unit is not affected by
an electrical noise.
- The place where air circulation in the room
will be good .
- There should not be any heat source or
steam near the unit
Confirm the positional relationship between
the unit and suspension bolts.
- Installation the ceiling opening to clean the
filter or service under the product.
Capacity
(kBtu/h)
9
800 (31-1/2)
12/18
800 (31-1/2)
[Unit:mm(inch)]
A
B
800 (31-1/2)
1,000 (39-3/8)
THE INDOOR UNIT INSTALLATION
Top view [Unit: mm(inch)]
Inspection hole
600 x 600
(23-5/8 x 23-5/8)
600
(23-5/8)
Side view [Unit: mm(inch)]
• Suitable dimension "H" is necessary to
get a slope to drain as shown in the figure
B(Min)
A(Min)
Service Space
7
Control box
Air outlet
600
(23-5/8)
Air outlet
H=20 (25/32)
or more
Ceiling
A
B

Publicidad

Capítulos

Tabla de contenido
loading

Tabla de contenido