IMPORTANT WARNIING: "Atc" and "btc" alarms can also occur in where the ambient temperature is high
or too low. Please note that in this case the ventilation of the place must be checked.
The "Atc" and "btc" alarms may lead to compressor failure and won´t covered by guarantee.
H.A.C.C.P ALARMS:
You can view the HACCP alarm events directly in the device's display. The following alarms are stored:
HA, maximum temperature alarm
PFA, extended power outage
OCF, exceeded maximum cycle time
To view the alarm of group press and hold SET key. The display will show the last alarm event. To view the alarm press
SET key.
To exit from the event, press the key SET.
With the
keys you can select, if present, the other alarms events of the group.
To exit from an alarm group, keep the SET key pressed for 3 seconds.
Indicates that there is a power failure alarm. Device warns of electricity is interrupted for a certain
time. Note: to return to normal working, pressing any key then restart the cycle.
Cycle doesn't reach to the set operation point. Check the loading capacity of the
product. For stopping the cycle press and hold chilling/freezing key for 3 seconds. If
you want to continue, do not act anything.
External Alarm. Contact authorized service.
External Alarm. Contact authorized service.
Door switch alarm. If the door remains open for more than 1 minute, the alarm will start.
Close the door. If the alarm continues control the door connections or contact technical
service.
Condenser overheated alarm. Condenser reaches to the first critical temperature.
Please plug out the product. Clean the condenser and wait 30 minutes. Then restart the
product again. If the alarm continues please contact technical service.
Condenser low temperature alarm. Control the ambient temperature. Clean the
condenser. Call authorized service.