Additional Safety Notes For Pa And Ff - Siemens SIPART PS2 6DR5.1-E Instrucciones De Operación

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 178
NOTICE
Standard cable gland/torque
Device damage.
Owing the reasons pertaining to tightness (IP enclosure rating) and the required tensile strength, only use the cables
having a diameter ≥ 8 mm for standard M20x1.5 cable gland, or use a suitable seal insert in case of smaller diameters.
In the NPT version, the positioner is delivered with a coupling. When inserting a counter piece in the coupling, ensure
that the maximum permissible torque of 10 Nm is not exceeded.
CAUTION
Maximum AC/DC switching voltage with UL approval E344532
The mechanical limit switch module 6DR4004-6K is approved for use for positioners with UL approval. The maximum
supply voltage in this case is 30 V AC/DC.
The mechanical limit switch module 6DR4004-8K is not approved for use for positioners with UL approval.
If this information is ignored, the UL approval for the mechanical limit switch module for the positioner becomes invalid.
Two-wire mode
NOTICE
Connection of voltage source to current input
Device damage if a voltage source is connected to the current input I
Never connect the current input I
Always use a voltage source with a maximum output current of I = 20 mA.
Note
Improvement of interference immunity
Lay signal cables separate from cables with voltages > 60 V.
Use cables with twisted wires.
Keep device and cables in distance to strong electromagnetic fields.
Take account of the conditions for communication specified in the Electrical data (Page 44).
HART: Use shielded cables to guarantee the full specification according to HART.
4.1.1

Additional safety notes for PA and FF

If the bus shield is fully effective, the interference immunity and the interference emission conform to the specifications. The
following measures ensure that the bus shield is fully effective:
● The shields have been connected to the metallic connections of the positioner.
● The shields have been laid up to the terminal boxes, the distributor and the transceiver.
Note
Dissipation of glitch impulses/equipotential bonding
In order to dissipate glitch impulses, the positioner must be connected to an equipotential bonding cable (earth potential)
using a low resistance. The positioner in the Makrolon enclosure is therefore equipped with an additional cable. Connect
the this cable to the shield of the bus cable and the equipotential bonding cable using a cable clamp.
Devices in the stainless steel or aluminum enclosure have a corresponding terminal on the outer side of the enclosure.
This terminal must also be connected to the equipotential bonding cable.
For applications in hazardous areas, ensure an adequately suitable equipotential bonding between the hazardous and
non-hazardous areas.
The positioner is equipped with an additional input (terminal 81 [+] and terminal 82 [-]) to approach the safety position. After
activating this function, this input must be continuously supplied with +24 V in order to retain the normal control function.
16
to a voltage source, otherwise the positioner may be destroyed.
w
(terminals 6 and 7).
w
SIPART PS2 (6DR5...)
A5E03436620-AB, 01/2017

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Sipart ps2 6dr5.2-e

Tabla de contenido