7.1.5
Certificates, approvals, explosion protection
Certificates and approvals
Classification according to pressure
equipment directive (PED 2014/68/EU)
CE conformity
UL conformity
See also
Certificates (http://www.siemens.com/processinstrumentation/certificates)
Explosion protection
Explosion protection
Explosion protection in accordance with
Intrinsic safety "i", "IS"
6DR5..0/1/2/3
•
6DR5..1/2/3
•
Dust, protection by means of enclosure "t", "DIP"
6DR5..1-0D/K...
•
6DR5..2-0D/K...
•
6DR5..3-0D/K...
•
6DR5..6-0E...
•
Increased safety, protection level "ec",
"nA", "ic"
6DR5..1/2/3-0D/F/G/K
•
Flameproof enclosure encapsulation "d",
"XP"
6DR5..5/6
•
Breakdown of the article numbers for assignment of the maximum permissible ambient temperature ranges
6DR5ayb-
a = 0, 2, 5, 6
y = 1, 2
b = 0, 1, 2, 3
42
For fluid group 1 gases; fulfills requirements according to article 4, paragraph
3 (good engineering practice SEP)
The applicable directives and applied standards with their revision levels can
be found in the EU declaration of conformity on the Internet.
You can find the appropriate "Standard(s) for Safety", including the relevant
versions, in the UL-CERTIFICATE OF COMPLIANCE on the Internet.
Ex markings
ATEX/IECEx
II 2 G Ex ia IIC T6/T4 Gb
II 3 G Ex ic IIC T6/T4 Gc
II 2 D Ex ia IIIC T110°C Db
II 2 D Ex tb IIIC T100°C Db
II 3 G Ex ec IIC T6/T4 Gc
II 2 G Ex d IIC T6/T4 Gb
0cdef-
c = E, G, D, F, K
d = G, N, M, P, R, S
e = 0, 1, 2, 3
f = 0, 1, 2, 3
FM/CSA
IS / I, II / 1 / A-D
IS / 1 / AEx / Ex ib / IIC, Gb
IS / III / 1 / E-G
IS / 21 / AEx / Ex ib / IIIC, Db, T110°C
CL.II, III, DIV.1, GP.EFG
ZN. 21, AEx tb IIIC T100°C Ta=85°C
NI / I / 2 / A-D
NI / 2 / (A)Ex / Ex nA, Ex ic / IIC, Gc
FM
XP, CL.I, DIV.1, GP.ABCD
XP, CL.I, ZN. 1, (A)Ex d IIC
CSA
XP. CL.I, DIV.1, GP.CD
XP, CL.I, ZN. 1, Ex d IIC
g..h-
g = 0, 2, 6, 7, 8
h = 0, 1, 2, 3, 4, 9
Z jjj
A20, A40, C20, D53, D54,
D55, D56, F01, K**, L1A,
M40,
R**, S**, Y**
* = any character
SIPART PS2 (6DR5...)
A5E03436620-AB, 01/2017