Construction
How does it work?
Range of stroke (linear actuator)
•
Angle of rotation (part-turn actuator)
•
Mounting method
On the linear actuator
•
On the part-turn actuator
•
Material
Enclosure C73451-A430-D78
•
Enclosure 6DR4004-1ES
•
Weight
Enclosure C73451-A430-D78
•
Enclosure 6DR4004-1ES
•
Torque for cable gland nut made of plastic
Electrical data
For connecting to circuits
with the following peak
values
Certificates and approvals
CE conformity
Explosion protection
Explosion protection in
accordance with
Intrinsic safety "i", "IS"
Permissible ambient
temperature
A
Appendix
A.1
Certificates
The certificates can be found on the DVD supplied and on the Internet at: Certificates
(http://www.siemens.com/processinstrumentation/certificates)
SIPART PS2 (6DR5...)
A5E03436620-AB, 01/2017
U
= 5 V
i
I
= 100 mA
i
P
= 160 mW
i
C
= negligibly small
i
L
= negligibly small
i
The applicable directives and applied standards with their revision levels can be found in
the EU declaration of conformity on the Internet.
ATEX/IECEx
II 2 G Ex ia IIC T6/T4 Gb
II 3 G Ex ic IIC T6/T4 Gc
3 to 130 mm (0.12 ... 5.12") (angle of rotation of the
positioner shaft 16 to 90°)
30 to 100°
Using mounting kit 6DR4004-8V and, where necessary,
an additional lever arm 6DR4004-8L on actuators
according to IEC 60534-6-1 (NAMUR) with a fin, columns,
or a plane surface.
Using mounting kit 6DR4004-8D on actuators with
mounting plane according to VDI/VDE 3845 and
IEC 60534-6-2: The required mount must be provided on
the actuator-side.
Makrolon® glass-fiber reinforced polycarbonate (PC)
Aluminum
Approx. 0.9 kg (1.98 lb)
Approx. 1.6 kg (3.53 lb)
See Construction (Page 40)
Ex markings
T4: -40 ... +90 °C (-40 ... +194 °F)
T6: -40 ... +60 °C (-40 ... +140 °F)
FM/CSA
IS / I, II / 1 / A-D
IS / 1 / AEx / Ex ib / IIC, Gb
53