This operation is possible only if the MEC-100 and the PC are communicating (On-line operating mode). To check
a parameter file without automatic applying to MEC-100, see Par. 5.6.3.
BE CAREFUL TO APPLY A CONFIGURATION SET TO THE MEC-100 WHEN THIS LAST IS COMMUNICATING
WITH THE OPERATING GENERATOR. Perform the above-mentioned operations to apply a configuration set to
the MEC-100 regulating the generator, involves a regulation setting alteration; it could be dangerous if the system
parameters are not properly set for the application. IT IS ALWAYS ADVISABLE TO LOAD A NEW
CONFIGURATION FILE WHEN THE MEC-100 IS NOT REGULATING THE GENERATOR.
5.6.3. Checking a Set of Parameters Off-line
To check a whole set of parameters without applying to MEC-100:
Interrupt the connection to the MEC-100.
Click the Database button in the menu bar of the MEC-100 Interface System (see Fig. 5.6.3.a).
In the displayed pull-down menu, point to the Open Parameter File Off-line item and click.
In the File Manager window, select the directory where the file to load is stored, select it and click on OK.
This operation only allows to check the configuration file: it is not possible to save a new configuration file in Off-line
operating mode.
963857137_G
Fig. 5.6.2.a
Loading a set of parameters
Fig. 5.6.3.a
Viewing a set of parameters offline
MEC-100
84