Configuration manual
4 Available devices in a Self consumption Installation
Below is a list of the devices available in a self consumption installation.
·
EMS energy manager.
·
Wattmeter.
·
Photovoltaic inverters.
·
Battery inverters (with photovoltaic generation).
·
Electric vehicle charging stations.
·
Electrical grid.
·
Diesel generator.
The following section, "INGECON SUN EMS Tools" , describes all the steps
required to configure the installation from the PC INGECON SUN EMS Tools
application, and the its different operating options.
All the devices are identified by defining the type of communication used with the energy
manager and its Modbus node.
Setting
Connection Type
Modbus node
Alias
(1)
As a general rule, the default communications port is 502. For charging stations the default
port is 503.
(2)
The default Modbus number for electric vehicle charging stations is 247.
To configure the Modbus node of a device, see the corresponding installation
manual.
Below are the configuration settings of all these devices.
Wattmeter
(2)
By default the wattmeter is A65.
44
Name used to identify the device
Setting
Power meter Type
Description
RS-485
(1)
IP Address / Port
Device Modbus node
(2)
Description
Type of wattmeter used