Configuration manual
6.2 A65+
Wattmeter with protective covers installed
Connections
The protective covers give protection against direct electrical contact. These must be removed to
make the connections and reinstalled once the connections are made.
Connect as shown in the following figure, installing current transformers on each phase.
See the section "Annex 3: Current transformer" for further information on the
transformers.
The wattmeter must be installed upstream from the power consumption and
production installation.
RS-485 communications are as indicated in the following table.
Pin
42
41
43
54
Signal
RS-485 B (+)
RS-485 A (-)
GND
A65 + wattmeter with protective covers removed
120 Ω
AAX2026IQM05_B.docx
Ingeteam